In case an irrigation event fails to cease:
- In the "Control Panel" section of Plantarray Client, verify that the valves open and close properly through manual operation.
- Check if there is a physical disturbance to the operation of the valve:
- Disconnect the controller from power, communication, and water.
- Use a manual or electric screwdriver to unscrew the 4 screws of the controller box circled below:
- Inside the controller box you will find the two valves wired to the PIU card as pictured below:
- Disconnect the valve from the PIU card.
- Open the valve mechanism by turning it and pull out the magnet with the spring.
- Check if there is anything that requires cleaning:
- Close the controller box, connect it back to power, communication and water, and check if the problem is solved.
- If the problem persists, please contact us.